Cable restraint test reports and configuration notes
Coated Cable Cleat Short-Circuit Test Report (PDL-26.160.04): the original laboratory PDF supplied to UES Promura was added on 19 October 2026. The report is dated 21 September 2026 and covers tests on 10–11 September 2026. The UES distributor code edition retains issuer details and all 31 report pages, with a cover explaining the code update. Report dates and test results are unchanged.
Short-circuit report register
Use the complete report, including test-rig photographs, cable details, currents, duration and verdict. Reports describe the objects and arrangements tested; they are not blanket approvals of every mounting method.
Coated Cable Cleat Short-Circuit Test Report (PDL-26.160.04) — tested configurations
The report covers CFFC-F1015M***-A900 arrangements at 300 mm and 600 mm fixed-cleat centres, including separate normally wrapped, double/triple cross-wrapped and bracket rigs. Match the complete arrangement to the project; a report is not a blanket rating for every mounting method.
Test programme (PDF, page 5) · Test results (PDF, pages 6-7). The report prints D70109 for its bracket rig; confirm assembly and bracket identity before applying a result.
Configuration checks
The current BAND-FAST Cable Cleat Solutions Brochure distinguishes cross-wrap, direct-to-rung and bracket arrangements. Historic summaries may use different examples. Do not carry a rating across arrangements simply because a part family is the same.
Coated Cable Cleat Short-Circuit Test Report (PDL-26.160.04) includes separate double/triple cross-wrap and bracket test rigs. Uncoated Cable Cleat Short-Circuit Test Report (PDL-26.160.07) distinguishes the uncoated arrangement with a liner from the bracket arrangement. Bracket references and complete assembly details must be confirmed before supply.
The manufacturer's unslotted result for one uncoated arrangement currently reports 117 kA at 300 mm, while the published BAND-FAST Cable Cleat Solutions Brochure table states 115 kA for its direct-to-rung arrangement and identifies bracket tests separately. Our calculator refers this unresolved combination to UES Promura for review instead of substituting a rating.
Request configuration and report confirmation · Return to calculator